FLANGED ENDS BUTT-WELD ENDS KNIFE GATE CLASS 150 Sizes 2''-12''

Cast stainless steel body and investment cast yoke. In fabricated valves, leakage of corrosive medium due to neglected maintenance on the packing, or line pressure surges causes corrosion and failure of most carbon steel or cast iron components. An all stainless steel valve offers better corrosion resistance than cast iron lined valves. The total cost of ownership becomes more attractive than the initial savings.

SPECIFICATIONS
Design API 600, ASME B 16.34
P-T Rating ASME B 16.34
Connections ASME B 16.5, 16.25
Face to Face ASME B 16.10
Test & Inspection API 598, RP 591
MATERIAL LIST
ITEM PARTS NAME MATERIALS Unless otherwise specified
1 Body A216 Gr WCB
2 Seat Ring/Facing A105 / Co-Cr-W Face or A216 Gr WCB / Co-Cr-W Face
3 Wedge 2"-6" A182 Gr F6a or A216 Gr WCB/13% Cr Face 8"-12" A216 Gr WCB / 13% Cr Face
4 Stem A182 Gr F6a
5 Backseat Bushing A276 Type 410
6 Gasket Flex Graphite w/ ss core
7 Bonnet A216 Gr WCB
8 Packing Graphoil w/ Braided Rings
9 Gland A182 Gr F6a
10 Gland Flange A105
11 Yoke Nut A439 Type D2
12 Yoke Bushing 2"-8" A536 Gr 65-45-12
Yoke Cap 10"-12" A216 Gr WCB
13 Handwheel A47Gr 32510
14 Handwheel Nut A47 Gr 32510
15 Gland Eyebolt Carbon Steel
16 Gland Eyebolt Nut A307 Gr B
17 Body Bonnet Stud A193 Gr B7
18 Body Bonnet Stud Nut A194 Gr 2H
19 Gland Eyebolt Pin Carbon Steel
20 Grease Fitting Carbon Steel
21 Set Screw Carbon Steel
22 Key Carbon Steel
23 Bolt Carbon Steel

  FLANGED ENDS BUTT-WELD KNIFE GATE VALVE

DIMENSIONS

Size Port Dia. Dia. Dia. Line Flange Thickness Bolt Circle Hole Dia Raised Face to BW Height Open Closed Stem Line Flange Bolts Quantity Size Turns to Hand- Weight
NPS N S D (min.) Dia. b k d Face Dia. g Face L L1 H H dv Open wheel Wd Approx.
INCHES INCHES INCHES INCHES INCHES INCHES INCHES INCHES INCHES INCHES INCHES INCHES INCHES INCHES lbs
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (metric) (mm) (kg)
2 2.00 50.8 2.11 53.6 6.00 152.4 0.62 15.7 4.75 120.7 0.75 19.1 3.62 91.9 7.00 177.8 8.50 215.9 16.29 413.8 13.58 344.9 0.75 19.1 4 5/8 M16 11.0 8.00 203.2 46 21
2-1/2 2.50 63.5 2.58 65.5 7.00 177.8 0.69 17.5 5.50 139.7 0.75 19.1 4.12 104.6 7.50 190.5 9.50 241.3 17.32 439.9 14.17 359.9 0.75 19.1 4 5/8 M16 12.6 8.00 203.2 62 28
3 3.00 76.2 3.07 78.0 7.50 190.5 0.75 19.1 6.00 152.4 0.75 19.1 5.00 127.0 8.00 203.2 11.13 282.7 19.68 499.9 16.14 410.0 0.88 22.2 4 5/8 M16 12.4 9.00 228.6 77 35
4 4.00 101.6 4.09 103.9 9.00 228.6 0.94 23.9 7.50 190.5 0.75 19.1 6.19 157.2 9.00 228.6 12.00 304.8 24.76 628.9 19.84 503.9 1.00 25.4 8 5/8 M16 14.8 10.00 254.0 117 53
5 5.00 127.0 5.10 129.5 10.00 254.0 0.94 23.9 8.46 215.0 0.87 22.0 7.31 185.7 10.00 254.0 15.00 381.0 28.38 720.8 22.64 575.0 1.13 28.6 8 3/4 M20 20.0 14.00 355.6 143 65
6 6.00 152.4 6.15 156.2 11.00 279.4 1.0 25.4 9.50 241.3 0.88 22.4 8.50 215.9 10.50 266.7 15.88 403.4 32.80 833.1 25.90 657.9 1.25 31.8 8 3/4 M20 13.6 10.50 266.7 207 94
8 8.00 203.2 8.15 207.0 13.50 342.9 1.12 28.4 11.75 298.5 0.88 22.4 10.62 269.7 11.50 292.1 16.50 419.1 40.74 1034.8 32.44 824.0 1.38 34.9 8 3/4 M20 16.5 16.00 406.4 348 158
10 10.00 254.0 10.20 259.1 16.00 406.4 1.19 30.2 14.25 362.0 1.00 25.4 12.75 323.9 13.00 330.2 18.00 457.2 50.11 1272.8 38.78 985.0 1.50 38.1 12 7/8 M22 22.8 18.00 457.2 524 238
12 12.00 304.8 12.24 310.9 19.00 482.6 1.25 31.8 17.00 431.8 1.00 25.4 15.00 381.0 14.00 355.6 19.75 501.7 58.66 1490.0 45.31 1150.9 1.63 41.3 12 7/8 M22 26.8 20.00 508.0 761 346


Tapping Valves and Isolation


Tapping valves are used to isolate main line media while the main line is tapped mechanically. Some tapping valves are designed to be used while the line is under working pressure and in operation, eliminating system downtime. We have done all the dirty work and reduced the never ending lists of tapping valves to our favorite cost effective, durable, time tested, dependable valves you will need for any job.

Tapping Valves Description

Tapping valves are installed using a variety of techniques, including hot tapping, wet tapping, line stopping or plugging, or pipe freezing. Other applications use tapping valves for installing flow meters, probes, or control valves into an existing line. Tapping valves may be installed using a hot tap or a wet tap technique. A hot tap or a wet tap is installed using a pressure-contained tapping machine to attach a tapping valve to the existing pipeline. Hot tapping uses a nozzle or split tee welded to the surface of the existing pressurized pipe. Hot taps are used in refineries, heating and cooling applications, and steam lines. Wet taps use a tapping sleeve that is bolted to the existing pipeline to make a branch connection. Wet tapping is used on sewer or water systems.

Need a tapping valve installation?

International Flow Technologies has been performing valve inserting on pipelines without shutting down the system for over 30 years. IFT can can install Valves indoors and outdoors on chilled and domestic water and air lines. Our customers include hospitals, industrial companies, mechanical contractors, military and municipalities. IFT is certified to complete your Tapping Valve so give use a call for a free quote: 1-800-545-1185